Equivalents: 2A-1403 is an equivalent of:
Belden A03142R,
General Cable 235050,
Lake Electronic Cable (LLC) V143,
Nexans 696823
Applications
Designed for power and control, telemetering, relay control, traffic control, switching, lighting and signal transmission. May be used in Class I, Div. 2 and Class II, Div. 2 Hazardous Locations per NEC Art. 501 and 502. These cables also conform to Art. 392 "Cable Trays" and Art 336 "Power and Control Tray Cable."
Specifications
INSULATION: Polyvinyl Chloride (PVC) per UL 62 for Type TFFN (18-16 AWG) or UL 83 for Type THWN or THHN wire, nominal thickness is 15 mils for sizes 18-12 AWG and 20 mils for 10 AWG
INSULATION JACKET: Each insulated conductor is jacketed with nylon meeting UL 62 for Type TFFN or UL 83 for Type THWN or THHN wire, minimum thickness is 4 mils
COLOR CODE: ICEA Method 1, Table E-2 (formerly K-2)
ASSEMBLY: Conductors are cabled with fillers where necessary to make round, two conductor cables are flat
OVERALL JACKET: 0.34" OD Sunlight-resistant Polyvinyl Chloride (PVC) per UL 1277
STANDARDS: Meets UL 1277 requirements for Type TC cables having THWN or THHN (TFFN) conductors, cables are listed for direct burial and meet the IEEE 1202, IEEE 383 and UL 1685 Btu/hr flame tests. Three conductor and larger constructions meet UL 1277 requirements for Exposed Runs and are rated